Victron
Victron MultiPlus-II 12/3000/120-32 Inverter/Charger
£1,274.40
/
Tax included.
PMP122305010
The Victron MultiPlus-II 12/3000/120-32 is a 12 V inverter/charger delivering 3000 VA continuous output (2400 W at 25°C), 5500 W peak, a 120 A battery charger and a 32 A AC transfer switch, with PowerAssist and ESS support.
✓
Collection or delivery in 1-2 weeks
Pickup available at Mercury Yacht Harbour
Usually ready in 2-4 days
Description
The Victron MultiPlus-II 12/3000/120-32 is a multifunctional inverter/charger for 12 V battery systems, combining a powerful sine wave inverter, a sophisticated battery charger and a high-speed AC transfer switch in a single compact enclosure. It is well suited to professional marine, vehicle and land based off-grid installations, and serves as a core component in a Victron Energy Storage System (ESS) with built-in anti-islanding for grid-connected use.
Its PowerControl and PowerAssist functions let it work alongside a limited shore or generator supply, first reducing charge current and then boosting the available power from the battery to prevent the source being overloaded. When the incoming supply fails, the inverter takes over the critical loads within milliseconds, so connected electronics keep running without interruption. An optional external AC current sensor extends current sensing for self-consumption optimisation and grid feed control.
A second AC output powers loads that should shut down when no external AC is present, and units can be paralleled or arranged for three-phase operation as systems grow. Configuration is handled through VEConfigure with an MK3-USB interface, while connecting a GX device such as a Cerbo GX adds local and remote monitoring through the free VRM portal.
PRODUCT DETAILS
- Combined 12 V inverter, 120 A charger and 32 A transfer switch in one unit
- 3000 VA continuous output, 2400 W at 25°C and 5500 W peak power
- PowerControl and PowerAssist prevent overload of shore or generator supplies
- Uninterrupted changeover to inverter in under 20 milliseconds
- Two AC outputs, with the second output live only when AC input is present
- Parallel and three-phase capable for higher power installations
- ESS ready with built-in anti-islanding for grid-connected systems
- GX and VRM ready for local and remote monitoring and control
No compatible transducers listed for this product.
No spares or accessories listed for this product.
No compatible products found.
Key specifications
| System voltage | 12 V |
| Continuous output power | 3000 VA |
| Continuous output power at 25°C | 2400 W |
| Peak power | 5500 W |
| Maximum charge current | 120 A |
| Transfer switch | 32 A |
Inverter
| DC input voltage range | 9.5 to 17 V |
| Output voltage / frequency | 230 VAC +/-2%, 50 Hz +/-0.1% |
| Cont. output power at 25°C (VA) | 3000 VA |
| Cont. output power at 25°C (W) | 2400 W |
| Cont. output power at 40°C (W) | 2200 W |
| Cont. output power at 65°C (W) | 1700 W |
| Peak power | 5500 W |
| Maximum efficiency | 93 % |
| Zero load power | 13 W |
| Zero load power in AES mode | 9 W |
Charger
| Charge voltage 'absorption' | 14.4 V |
| Charge voltage 'float' | 13.8 V |
| Storage mode | 13.2 V |
| Maximum charge current | 120 A |
| Battery temperature sensor | Yes |
Connectivity & control
| VE.Bus communication port | For parallel and three phase operation, remote monitoring and system integration |
| General purpose comms port | Yes, 2x |
| Programmable relay | Yes (general alarm, DC under voltage or genset start/stop) |
| Remote on/off | Yes |
| External AC current sensor (optional) | 50 A or 100 A |
Protection
| Protection | Output short circuit, overload, battery voltage too high, battery voltage too low, temperature too high, 230 VAC on inverter output, input voltage ripple too high |
Environmental
| Operating temperature range | -40 to +65 °C (fan assisted cooling) |
| Humidity (non-condensing) | Max. 95 % |
| Maximum altitude | 2000 m |
Physical
| Material & colour | Steel, blue RAL 5012 |
| Protection category | IP22 |
| Battery connection | M8 bolts |
| 230 VAC connection | Screw terminals 13 mm² (6 AWG) |
| Weight | 19 kg |
| Dimensions (h x w x d) | 546 x 275 x 147 mm |
Conformance
| Safety | EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2 |
| Emission / Immunity | EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3, IEC 61000-6-1/-6-2/-6-3 |
No downloads available for this product.
How fast does the MultiPlus-II switch to battery power during a grid failure?
The transfer to inverter operation happens in less than 20 milliseconds, so computers and other electronic equipment continue to operate without disruption.
What do PowerControl and PowerAssist do?
PowerControl lets you set a maximum shore or generator current; the unit then uses only the spare capacity for battery charging to avoid overloading the source. PowerAssist goes further by adding battery power to support the supply during short peaks, then recharges the battery when the load drops.
Can MultiPlus-II units be used in parallel or three-phase systems?
Yes. Up to six units can be connected in parallel for higher output, and three units of the same model can be configured for three-phase operation, with up to six sets of three paralleled for larger systems.
Is an external current sensor required?
No, it is optional. An external AC current sensor (50 A or 100 A) can be added to extend the PowerControl and PowerAssist range and to optimise self-consumption with external current sensing.
Can the MultiPlus-II be monitored remotely?