Victron
Victron MultiPlus-II 48/15000/200-100 Inverter/Charger
£2,800.80
/
Tax included.
PMP483150000
Victron MultiPlus-II 48/15000/200-100: 15000 VA continuous (12000 W at 25°C), 27000 W peak, 200 A charger, 100 A transfer; PowerAssist and ESS.
✓
Collection or delivery in 1-2 weeks
Pickup available at Mercury Yacht Harbour
Usually ready in 2-4 days
Description
The Victron MultiPlus-II 48/15000/200-100 is the flagship single unit in the range, bringing together a high-power sine wave inverter, a 200 A battery charger and an automatic AC transfer switch in one heavy-duty enclosure. It supplies a clean and stable 230 VAC output for the most demanding single-phase loads, while the integrated charger restores the battery bank whenever shore power or a generator is present. Transfer between mains and inverter operation is automatic and completes in under 20 milliseconds, keeping sensitive electronics running seamlessly through any grid interruption.
PowerControl lets you set a maximum shore or generator current so that only the spare capacity is used for charging and a limited source is never overloaded. PowerAssist takes this further by adding battery power to the supply to absorb short, heavy peaks, then recharging as soon as demand drops. An optional external AC current sensor (50 A or 100 A) extends this range and helps optimise self-consumption, while the second AC output is well suited to shedding non-critical loads. The unit is ESS ready with built-in anti-islanding for grid-parallel energy storage, and it is configured using VEConfigure through an MK3-USB interface, with full monitoring and remote control via a GX device and the free VRM portal.
As the largest of the high-power models, this 15 kVA unit can be paralleled for even greater output only when an external AC transfer switch is fitted; the 8 kVA, 10 kVA and 15 kVA models all share this requirement so that large single-phase and three-phase systems remain safely coordinated. A substantial steel housing, full protection suite and wide operating temperature range make it ideal for large marine, off-grid and backup installations.
PRODUCT DETAILS
- Combined 48 V inverter, 200 A battery charger and 100 A AC transfer switch in one unit
- 15000 VA continuous output, 12000 W at 25°C, 27000 W peak
- PowerControl and PowerAssist manage limited shore or generator supplies
- Automatic changeover to inverter in under 20 ms protects sensitive equipment
- Two AC outputs allow non-critical loads to be shed automatically
- Parallel and three-phase capable using an external AC transfer switch
- ESS ready with built-in anti-islanding for grid-parallel energy storage
- GX and VRM monitoring with VEConfigure setup via MK3-USB
No compatible transducers listed for this product.
No spares or accessories listed for this product.
No compatible products found.
Key specifications
| System voltage | 48 V |
| Continuous output power | 15000 VA |
| Continuous output power at 25°C | 12000 W |
| Peak power | 27000 W |
| Maximum charge current | 200 A |
| Transfer switch | 100 A |
Inverter
| DC input voltage range | 38 to 66 V |
| Output voltage / frequency | 230 VAC +/-2%, 50 Hz +/-0.1% |
| Cont. output power at 25°C (VA) | 15000 VA |
| Cont. output power at 25°C (W) | 12000 W |
| Cont. output power at 40°C (W) | 10000 W |
| Cont. output power at 65°C (W) | 7000 W |
| Peak power | 27000 W |
| Maximum efficiency | 95 % |
| Zero load power | 55 W |
| Zero load power in AES mode | 39 W |
Charger
| Charge voltage 'absorption' | 57.6 V |
| Charge voltage 'float' | 55.2 V |
| Storage mode | 52.8 V |
| Maximum charge current | 200 A |
| Battery temperature sensor | Yes |
Connectivity & control
| VE.Bus communication port | For parallel and three phase operation, remote monitoring and system integration |
| General purpose comms port | Yes, 2x |
| Programmable relay | Yes (general alarm, DC under voltage or genset start/stop) |
| Remote on/off | Yes |
| External AC current sensor (optional) | 50 A or 100 A |
Protection
| Protection | Output short circuit, overload, battery voltage too high, battery voltage too low, temperature too high, 230 VAC on inverter output, input voltage ripple too high |
Environmental
| Operating temperature range | -40 to +65 °C (fan assisted cooling) |
| Humidity (non-condensing) | Max. 95 % |
| Maximum altitude | 2000 m |
Physical
| Material & colour | Steel, blue RAL 5012 |
| Protection category | IP22 |
| Battery connection | Four M8 bolts |
| 230 VAC connection | Bolts M6 |
| Weight | 80 kg |
| Dimensions (h x w x d) | 810 x 405 x 217 mm |
Conformance
| Safety | EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2 |
| Emission / Immunity | EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3, IEC 61000-6-1/-6-2/-6-3 |
No downloads available for this product.
How fast does the MultiPlus-II switch to battery power during a grid failure?
The transfer to inverter operation happens in less than 20 milliseconds, so computers and other electronic equipment continue to operate without disruption.
What do PowerControl and PowerAssist do?
PowerControl lets you set a maximum shore or generator current; the unit then uses only the spare capacity for battery charging to avoid overloading the source. PowerAssist goes further by adding battery power to support the supply during short peaks, then recharges the battery when the load drops.
Can these high-power models be paralleled?
Yes, but the 8 kVA, 10 kVA and 15 kVA models can only be connected in parallel when an external AC transfer switch is used; see the MultiPlus-II External Transfer Switch application manual.
Is an external current sensor required?
No, it is optional. An external AC current sensor (50 A or 100 A) can be added to extend the PowerControl and PowerAssist range and to optimise self-consumption with external current sensing.
Can the MultiPlus-II be monitored remotely?
Yes. When connected to a GX device such as a Cerbo GX, system data can be stored and viewed on the free VRM portal, and settings can be changed remotely over the internet.